Roof Runoff & Downpipe Sizer
Roof area + rain intensity → downpipes needed
Category: Water, power & services
What you enter
- Roof / terrace area (sq ft)
- Design rain intensity: Heavy shower · 50 mm/hr, Design storm · 100 mm/hr, Extreme cloudburst · 150 mm/hr
An example
With the starting values (Roof / terrace area (sq ft): 1000; Design rain intensity: Heavy shower · 50 mm/hr), it gives:
- Peak runoff: 77 L/min
- 100 mm dia rainwater pipes: 2 nos
- …or 75 mm dia pipes: 2 nos
Good to know
NBCS 2026 Part E, Table 25: a 100 mm rainwater pipe drains about 84 m² of flat roof at 100 mm/hr and 56 m² at 150 mm/hr; a 75 mm pipe about 41 m² and 27 m². Always provide at least two outlets, keep them at low points with khurras, and never reduce pipe size below the outlet. Kolkata cloudbursts regularly exceed 50 mm/hr — undersized RWPs are why terraces pond.
Sources
- NBCS 2026 (SP 7:2026) Part E Sec 2, Table 25 (rainwater pipes for roof drainage; read 28 Nov 2026)
- IS 2527:1984 (roof drainage)
Checked 7 Oct 2026, pending our team’s sign-off.
Free, instant and indicative: a starting point for our engineers’ estimate, not a substitute for one.